Customization: | Available |
---|---|
Certification: | RoHS, CB, ISO9001, CE |
Working Medium: | R410A |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Market model | WBC-85.0H-A-S(VE-L1) | WBC-170H-A-S(VE-L1) | ||
Heating Working Condition A -12/14ºC W 36-41ºC |
Output Capacity | Kw | 51.08 | 102.16 |
COP | - | 2.52 | 2.52 | |
Input Power | KW | 20.27 | 40.59 | |
Input Current | A | 36.26 | 73.85 | |
Heating Working Condition A 20ºC W 15-80ºC |
Output Capacity | Kw | 80 | 160 |
COP | - | 3.42 | 3.42 | |
Input Power | Kw | 23.39 | 46.78 | |
Input Current | A | 41.85 | 83.69 | |
Power Supply | V/PH/HZ | 380V/3/50HZ | ||
Max input power | KW | 35.09 | 70.06 | |
Max running current | A | 62.77 | 118.34 | |
Working Ambeint Temperature | ºC | -30~45 | ||
Water Flow Rate | m³/h | 13.8 | 27.5 | |
water pressure loss | Kpa | 60 | 80 | |
Thermostat Factory Setting(Heating/Cooling) | ºC | 41/7 | ||
Thermostat Maximun Setting(Heating/Cooling) | ºC | 60/5 | ||
Sound pressure Level @1m | dB(A) | 68 | 70 | |
Net Dimension (L*W*H) | mm | 1480/1200/2375 | 2600/1280/2475 | |
Net Weight | kg | 650 | 1108 | |
Remarks:The Specifications are subject to changes without notice. |