Basic Info.

Model NO.
VE-L1
Heat Source Type
Air Source Heat Pump
Thermostat Factory Setting
41/7
Thermostat Maximum Setting
60/5
Ambient Working Temperature
-30c~45c
Compressor
Copeland Scrool
Heating Capacity
170kw
Unit Type
Inverter
Application Scope
Hotels,Clubs,Hospitals,Villas and etc
Transport Package
Factory Standard
Specification
2600*1280*2475mm
Trademark
Wotech
Origin
China
HS Code
84186120

Product Description

R410a Commercial air to water Heat Pump with full inverter and EVI system 
Features:

1.Hot water up to 60ºC,suitable for underfloor/radiator heating

2.With EVI system,can work stable at ambient temperature -30C to 45C

3.Full inverter system,Stable and efficient performance.

4.R410a System,environment friendly

5.Application Scope:Hotels,clubs,hospitals,villas and any place in need of air conditioning,heating and hot water

6.With Wifi App control
R410A Commercial Air to Water Heat Pump with Full Inverter and Evi System

R410A Commercial Air to Water Heat Pump with Full Inverter and Evi System

Installation Diagram:
 
R410A Commercial Air to Water Heat Pump with Full Inverter and Evi System
R410A Commercial Air to Water Heat Pump with Full Inverter and Evi System


R410A Commercial Air to Water Heat Pump with Full Inverter and Evi System

Technical Parameter
Market model WBC-85.0H-A-S(VE-L1) WBC-170H-A-S(VE-L1)
Heating Working Condition
A -12/14ºC     W 36-41ºC
Output Capacity Kw 51.08 102.16
COP  - 2.52 2.52
Input Power  KW 20.27 40.59
Input Current A 36.26 73.85
Heating Working Condition
A 20ºC    W 15-80ºC
Output Capacity Kw 80 160
COP - 3.42 3.42
Input Power Kw 23.39 46.78
Input Current A 41.85 83.69
Power Supply V/PH/HZ 380V/3/50HZ
Max input power KW 35.09 70.06
Max running current A 62.77 118.34
Working Ambeint Temperature ºC -30~45
Water Flow Rate m³/h 13.8 27.5
water pressure loss Kpa 60 80
Thermostat Factory Setting(Heating/Cooling) ºC 41/7
Thermostat Maximun Setting(Heating/Cooling) ºC 60/5
Sound pressure Level @1m dB(A) 68 70
Net Dimension (L*W*H)  mm 1480/1200/2375 2600/1280/2475
Net Weight kg 650 1108
Remarks:The Specifications are subject to changes without notice.
Key Components:

R410A Commercial Air to Water Heat Pump with Full Inverter and Evi System
Manufacturing & Laboratories
R410A Commercial Air to Water Heat Pump with Full Inverter and Evi System

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier